DailyAds.pk
Saved

Public Safety Notice — Mandatory Building Fire & Life-Safety Requirements (Government of the Punjab)

Public Safety Notice · Lahore · Dunya,

Notice advertisement published in Dunya on Thursday, 3 September 2026, listed under Lahore, Pakistan. Issued by Public Safety Notice.

Newspaper clipping: Public Safety Notice — Mandatory Building Fire & Life-Safety Requirements (Government of the Punjab), Dunya, 03 Sep 2026 Open the full-size clipping
Original clipping · Dunya · 03 Sep 2026 · tap to zoom

Advertisement details

Issuer: Emergency Services Department, Government of the Punjab (Rescue 1122). Purpose: Mandatory building safety and fire-protection measures to protect life and property. Building owners and managers are required to ensure the following systems, arrangements and clearances are in place; non-compliance may make the owner liable for any loss of life or property.

RequirementDetails / Minimum Standard
Safety ManagementAppoint a Safety Manager & Emergency Response Team; conduct regular evacuation drills and daily safety inspections.
Encroachment-free AccessBuildings must be located on a minimum 30-foot unobstructed road.
Emergency StaircasesMaximum 100 feet apart; provide signage, floor marking and emergency lights; must be ventilated and unobstructed.
Basement AccessAt least two exits on opposite sides; no hazardous material, boiler or kitchen in basement.
Smoke & Flame Detection / IR Cameras & AlarmInstalled in all common areas and corridors with uninterrupted power supply and 24/7 surveillance by trained safety/security staff.
Fire Alarm SystemAudible and visual appliances; manual pull stations or push-button call points near exits.
Internal Standpipe System (Wet Riser)On each floor with 2.5 inch diameter coupling and 1.5 inch hose with nozzle.
Automatic Sprinkler SystemRequired in all spaces containing combustible material.
Floor Separators in Electrical DuctsSeparation by 4mm metal sheet and fire-resistant sealants around cable penetrations.
Fire Dampers in HVACInstall fire dampers and insulate ducts with fire-retardant materials.
Fire ExtinguishersDCP-6kg near exits; maximum 75 ft between extinguishers; provision of one per 2,000 sq. ft. of floor area.
First Aid & Escape MasksProvide a first aid box and two fire escape masks at each floor entrance, security posts, reception or nursing stations.
External Fire HydrantRed pillar type at safe, easily accessible points with two outlets of 2.5" diameter and instantaneous coupling.
Liability for Non-ComplianceOwner shall be liable for any loss of life or property in case of non-compliance.

Contact/Enforcement: Emergency Services Department (Rescue 1122), Government of the Punjab. Follow local enforcement and compliance instructions issued by the department.

Published in Dunya on Thursday, 3 September 2026. DailyAds.pk indexes newspaper advertisements; the original notice and the issuing organisation remain the source for final terms and eligibility.

Dunya · 03 Sep 2026