· Pakistan’s newspaper advertisement archive
DailyAds.pk
Saved

Public Safety Checklist for Buildings — Emergency Services Department, Government of the Punjab

Public Safety Checklist for Buildings · Lahore · Jang,

Notice advertisement published in Jang on Thursday, 3 September 2026, listed under Lahore. Issued by Public Safety Checklist for Buildings.

Similar notices

All notices

Advertisement details

Issued by the Emergency Services Department, Government of the Punjab (Rescue 1122). This public notice outlines mandatory fire-safety and emergency preparedness requirements for buildings to protect life and property. Non-compliance may render the owner liable for loss of life or property.

RequirementDetails / Minimum Standard
Safety ManagementDesignated Safety Manager & Emergency Response Team; regular evacuation drills and daily safety inspections.
Encroachment-free AccessBuilding must be located on a minimum 30 ft unobstructed road.
Emergency StaircasesMaximum 100 ft apart; must have signage, floor markings and emergency lights; ventilated and unobstructed.
Basement AccessAt least two exits on opposite sides; no hazardous material, boilers or kitchens allowed in basement.
Floor Separators in Electrical DuctsSeparated by 4 mm metal sheet and sealed with fire-resistant sealants around cables.
Fire ExtinguishersDCP 6 kg units near exits; maximum 75 ft spacing; one per 2,000 sq ft floor area.
External Fire HydrantRed pillar type at safe, easily accessible points with two outlets of 2.5" dia and instantaneous coupling.
Smoke & Flame Detection / CCTVIR cameras and alarm system in common areas & corridors with uninterrupted power and 24/7 surveillance by trained staff.
Fire Alarm SystemAudible & visual appliances; manual pull stations or push-button call points near exits.
Internal Stand Pipe (Wet Riser)On each floor with 2.5" diameter coupling and 1.5" hose with nozzle.
Automatic Sprinkler SystemRequired in spaces having any combustible material.
Fire Dampers in HVACFire dampers and insulation of ducts with fire-retardant materials.
First Aid & Escape EquipmentFirst aid box and two fire escape masks at each floor entrance, security posts and reception or nursing stations.

Owners and managers should implement these measures immediately to ensure compliance and protect occupants. For emergency response and fire safety services see Rescue 1122.

Published in Jang on Thursday, 3 September 2026. DailyAds.pk indexes newspaper advertisements; the original notice and the issuing organisation remain the source for final terms and eligibility.